You can’t buy a spray foam that’s 2 hour fire rated on its own. That rating only ever goes to a whole wall, floor or ceiling that got tested in a lab as one piece. Spray foam can be one of the layers inside a 2 hour wall, though. By itself, most spray foam gets a Class 1 surface burning score, and you still have to cover it (usually with 1/2-inch drywall) anywhere people live.
We get this call a few times a year. A builder needs a 2 hour wall between two townhomes and asks us to “just spray the 2 hour foam.” We have to tell them it doesn’t exist as a product. The rating comes from how the whole wall is put together. Learning that at framing inspection costs a lot more than learning it now, so let’s sort out what each rating actually covers.
Which Fire Ratings Can Spray Foam Meet?
Rating or rule
What it measures
Does spray foam meet it alone?
Class 1 (Class A) flame spread
Flame spread of 25 or less on the surface (ASTM E84)
Many products do, at a tested thickness
IRC R316.3 limits
Flame spread of 75 or less and smoke of 450 or less
Yes, for code-approved foam
15-minute thermal barrier
A cover that protects foam from a room fire
No, the foam needs this cover
Ignition barrier
A lighter cover in attics and crawl spaces
No, unless the product is approved without one
1, 2 or more hour fire resistance
A full wall or floor holding back fire for that long
Only as part of a tested assembly
NFPA 285
Fire spread on exterior walls of some commercial buildings
Only as part of a tested wall design
Why Can't Spray Foam Be 2 Hour Fire Rated by Itself?
Because at the end of the day, it’s plastic. Two liquids meet at the spray gun and puff up in the wall (our guide to SPF insulation has the chemistry). Get polyurethane hot enough and it’ll burn. The fire retardants mixed in buy some time. They don’t change what it is.
An hour rating answers one question: how long does this whole wall keep fire on one side and stay standing? The answer depends on the studs, the screws, the insulation and, more than anything, the drywall. In most rated walls, layers of Type X drywall are doing the hard work. The foam is along for the ride.
So if someone asks for “2 hour spray foam,” what they really need is a 2 hour wall that’s approved with spray foam inside it.
Can a 2 Hour Fire Rated Wall Include Spray Foam?
It can, if somebody already tested that exact wall. Foam manufacturers pay labs to burn specific wall designs with their product inside. Two you can look up:
ICC-ES listing ESL-1373 shows an open-cell spray foam inside a load-bearing double-stud wall rated for 2 hours under ASTM E119.
BASF reports 25 UL-rated wall designs and 16 floor-ceiling designs that include its spray foam, with ratings from 45 minutes to 4 hours.
Treat the listing like a recipe you can’t improvise on. Swap 2×6 studs for 2x4s, use a different foam, or skip a layer of drywall, and you may not have a rated wall anymore. Build it the way the listing says, and show it to your building official before you start.
What Fire Rating Does Spray Foam Have on Its Own?
Just a surface burning rating. In the ASTM E84 tunnel test, lots of spray foams post a flame spread of 25 or under, which gets them called Class 1 (or Class A). The residential code (IRC Section R316.3) only asks for 75 or under on flame spread and 450 or under on smoke.
That test watches flame race along the face of the material. It never asks how long a wall can hold a fire back. So “Class 1” on the bucket and “2 hour” on the plans are talking about two completely different things.
Does Spray Foam Need a Thermal Barrier?
Almost always, if people live in that space. IRC Section R316.4 and IBC Section 2603.4 say foam plastic has to be separated from the inside of the building by an approved thermal barrier. The standard one is 1/2-inch drywall. Installers call it the “15-minute barrier,” since it’s there to keep a room fire off the foam for roughly that long.
Some foams are approved to go without drywall if they’re coated with a specific intumescent paint, a coating that swells into a thick, insulating char when it heats up. Those approvals come from the product’s evaluation report, like an ICC-ES report, and the coating type and thickness have to match that report exactly.
What Is an Ignition Barrier?
It’s a lighter cover that’s allowed in attics and crawl spaces people only go into for repairs. IRC Sections R316.5.3 and R316.5.4 cover those spaces. Some spray foams are approved there without a separate ignition barrier, and again, that approval comes from the evaluation report. You can read more in our guides on whether spray foam insulation is safe and crawl space spray foam.
What About Foam Kits and Cans Labeled Fire Rated?
Walk down the insulation aisle and you’ll see “fire rated” on all kinds of cans. It can mean three very different things:
DIY spray foam kits are often marked Class 1. That’s the surface burning rating. It isn’t an hour rating, and the foam still needs a thermal barrier.
Firestop foams are for sealing holes in rated walls, and they carry listings for specific openings. Nobody uses them to insulate a wall.
Thermal barrier coatings are paints sprayed over foam so it can be left exposed. They protect the foam. They don’t give the wall an hour rating.
Need an hour rating? Ask for the tested wall design. No label on a can will get you there.
When Does a Home Need a 1 or 2 Hour Fire Rated Wall?
Most single-family homes in Denver never need one. Here’s when they come up:
Situation
Typical rule
Townhouse shared walls
Rated separation, often 1 or 2 hours depending on construction and sprinklers
Duplex unit separations
Rated separation between the units
Exterior walls very close to a property line
Rated wall where the IRC requires it
Apartments and commercial buildings
Rated walls, floors and corridors under the IBC
Attached garage
Specific drywall separation, not an hour-rated wall in most homes
For an attached garage, the IRC calls for 1/2-inch drywall on the garage side of the house wall and 5/8-inch Type X drywall under rooms above. Our DIY garage insulation guide goes through it. If you’re working on a larger building, see our commercial insulation services.
How Should Openings Be Sealed in a Fire Rated Spray Foam Wall?
Any hole for a pipe or wire through a rated wall needs a listed firestop system. Regular spray foam isn’t a firestop, and neither is orange “fire block” foam unless a listed system names it for that exact opening. Our guide to firestop insulation breaks down firestopping, fireblocking and fire rated insulation.
Is Open-Cell or Closed-Cell Spray Foam Better for Fire Safety?
On fire, it’s a tie. Both need a thermal barrier in living areas, so choose based on the job instead:
Closed-cell has a higher R-value per inch and shrugs off water. It’s our go-to for basements, crawl spaces and rim joists. Learn more about what closed-cell spray foam is.
Open-cell is softer and cheaper per inch. It works well in interior walls and rooflines, and it’s the type used in the ESL-1373 rated wall above.
Build Fire Ratings With Tested Systems, Not Product Labels
If you remember one thing, make it this: the hour rating lives in the wall design, not in the foam. Spray foam can sit inside a tested 2 hour wall and can pass Class 1 surface burning limits. It still needs drywall (or an approved coating) over it in living spaces and a listed firestop at every hole.
Grizzly Insulation Co installs open-cell and closed-cell spray foam with the right code protections in place. Our BPI Certified team will tell you exactly what your project needs before any work starts.
2 Hour Fire-Rated Spray Foam Insulation: What Fire Ratings Spray Foam Can Actually Meet
You can’t buy a spray foam that’s 2 hour fire rated on its own. That rating only ever goes to a whole wall, floor or ceiling that got tested in a lab as one piece. Spray foam can be one of the layers inside a 2 hour wall, though. By itself, most spray foam gets a Class 1 surface burning score, and you still have to cover it (usually with 1/2-inch drywall) anywhere people live.
We get this call a few times a year. A builder needs a 2 hour wall between two townhomes and asks us to “just spray the 2 hour foam.” We have to tell them it doesn’t exist as a product. The rating comes from how the whole wall is put together. Learning that at framing inspection costs a lot more than learning it now, so let’s sort out what each rating actually covers.
Which Fire Ratings Can Spray Foam Meet?
Why Can't Spray Foam Be 2 Hour Fire Rated by Itself?
Because at the end of the day, it’s plastic. Two liquids meet at the spray gun and puff up in the wall (our guide to SPF insulation has the chemistry). Get polyurethane hot enough and it’ll burn. The fire retardants mixed in buy some time. They don’t change what it is.
An hour rating answers one question: how long does this whole wall keep fire on one side and stay standing? The answer depends on the studs, the screws, the insulation and, more than anything, the drywall. In most rated walls, layers of Type X drywall are doing the hard work. The foam is along for the ride.
So if someone asks for “2 hour spray foam,” what they really need is a 2 hour wall that’s approved with spray foam inside it.
Can a 2 Hour Fire Rated Wall Include Spray Foam?
It can, if somebody already tested that exact wall. Foam manufacturers pay labs to burn specific wall designs with their product inside. Two you can look up:
Treat the listing like a recipe you can’t improvise on. Swap 2×6 studs for 2x4s, use a different foam, or skip a layer of drywall, and you may not have a rated wall anymore. Build it the way the listing says, and show it to your building official before you start.
What Fire Rating Does Spray Foam Have on Its Own?
Just a surface burning rating. In the ASTM E84 tunnel test, lots of spray foams post a flame spread of 25 or under, which gets them called Class 1 (or Class A). The residential code (IRC Section R316.3) only asks for 75 or under on flame spread and 450 or under on smoke.
That test watches flame race along the face of the material. It never asks how long a wall can hold a fire back. So “Class 1” on the bucket and “2 hour” on the plans are talking about two completely different things.
Does Spray Foam Need a Thermal Barrier?
Almost always, if people live in that space. IRC Section R316.4 and IBC Section 2603.4 say foam plastic has to be separated from the inside of the building by an approved thermal barrier. The standard one is 1/2-inch drywall. Installers call it the “15-minute barrier,” since it’s there to keep a room fire off the foam for roughly that long.
Some foams are approved to go without drywall if they’re coated with a specific intumescent paint, a coating that swells into a thick, insulating char when it heats up. Those approvals come from the product’s evaluation report, like an ICC-ES report, and the coating type and thickness have to match that report exactly.
What Is an Ignition Barrier?
It’s a lighter cover that’s allowed in attics and crawl spaces people only go into for repairs. IRC Sections R316.5.3 and R316.5.4 cover those spaces. Some spray foams are approved there without a separate ignition barrier, and again, that approval comes from the evaluation report. You can read more in our guides on whether spray foam insulation is safe and crawl space spray foam.
What About Foam Kits and Cans Labeled Fire Rated?
Walk down the insulation aisle and you’ll see “fire rated” on all kinds of cans. It can mean three very different things:
Need an hour rating? Ask for the tested wall design. No label on a can will get you there.
When Does a Home Need a 1 or 2 Hour Fire Rated Wall?
Most single-family homes in Denver never need one. Here’s when they come up:
For an attached garage, the IRC calls for 1/2-inch drywall on the garage side of the house wall and 5/8-inch Type X drywall under rooms above. Our DIY garage insulation guide goes through it. If you’re working on a larger building, see our commercial insulation services.
How Should Openings Be Sealed in a Fire Rated Spray Foam Wall?
Any hole for a pipe or wire through a rated wall needs a listed firestop system. Regular spray foam isn’t a firestop, and neither is orange “fire block” foam unless a listed system names it for that exact opening. Our guide to firestop insulation breaks down firestopping, fireblocking and fire rated insulation.
Is Open-Cell or Closed-Cell Spray Foam Better for Fire Safety?
On fire, it’s a tie. Both need a thermal barrier in living areas, so choose based on the job instead:
Our guide to the right foam insulation for a Denver home compares the two. And if fire resistance inside the wall is what you care about most, mineral wool doesn’t burn at all. See our guide on whether Rockwool is fireproof.
Build Fire Ratings With Tested Systems, Not Product Labels
If you remember one thing, make it this: the hour rating lives in the wall design, not in the foam. Spray foam can sit inside a tested 2 hour wall and can pass Class 1 surface burning limits. It still needs drywall (or an approved coating) over it in living spaces and a listed firestop at every hole.
Grizzly Insulation Co installs open-cell and closed-cell spray foam with the right code protections in place. Our BPI Certified team will tell you exactly what your project needs before any work starts.
Learn more about our spray foam insulation service and Denver spray foam insulation, or call (303) 854-6221.
Frequently Asked Questions About 2 Hour Fire Rated Spray Foam
Yes and no. Lots of spray foams have a Class 1 surface burning rating. None has an hour rating by itself.
Only if that exact wall design was tested and listed with that specific spray foam product. Build it exactly as listed.
In living spaces, yes, or an approved coating. The standard thermal barrier is 1/2-inch drywall.
It’s a plastic, so yes, it can burn. Fire retardants slow ignition, but without a cover it can still catch.
The foam scored a flame spread of 25 or less under ASTM E84. That’s a surface burning score, not a measure of how long a wall holds back fire.
Sometimes. Some products are approved without an ignition barrier in attics that people only enter for repairs. Check the product’s evaluation report.